Drooping Reference
Program  Feedback  Drooping Control
This parameter sets the method to be used in determining the output
torque while operating in the Drooping Control mode.
Settings:
0 — Total Torque Calculated by the Detection Current.
1 — Torque without Acc/Dec Torque Calculated by Detection Current.
2 — Total Torque Calculated by the Command Current.
3 — Torque without Acc/Dec Torque Calculated by the Command
Current.
Light-Load High-Speed Operation
Program  Special  Crane/Hoist Load
This parameter enables the Light-Load High-Speed function by selecting
an operating mode. The Light-Load High-Speed function accelerates the
output frequency of the ASD from the programmed speed to the setting
.
established in
F341
This parameter may be disabled.
If either of the other selections are made and configured, and after the
criteria of
F331
F333
are met, the Light-Load High-Speed function is
enabled and this parameter determines the operating mode of the Light-
Load High-Speed function.
Settings:
0 — Disabled
1 — Reserved
2 — Automatic Enable - Automatic Speed (F341)
3 — Automatic Enable - Preset Speed (Preset ID
1000
)
Bin
4 — Discrete Enable - Automatic Speed (F341) (see item 60 of
8 on pg.
170)
5 — Discrete Enable - Preset Speed (Preset ID
(see item 60 of
Table 8 on pg.
Light-Load High-Speed Operation Switching Lower-Limit Frequency
Program  Special  Crane/Hoist Load
This parameter sets an output frequency threshold that, once
surpassed, allows the Light-Load High-Speed function to be used.
The Light-Load High-Speed function may be used if the frequency
threshold (F331) and the following conditions are met:
1) Light-Load High-Speed Operation Enable is configured at F330.
2) The output torque is less than the setting established in
reaching the frequency setting here.
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
is OR'ed w/
Bin
Table
is OR'ed w/1000
Bin
170)
F335
when
F327-F331
Direct Access Number — F327
Parameter Type — Selection List
Factory Default — Total torque
calculated by the detection current
Changeable During Run — Yes
Direct Access Number — F330
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Minimum — 30.0
Maximum — Upper-Limit (
Units — Hz
)
Bin
Direct Access Number — F331
Parameter Type — Numerical
Factory Default — 40.00
Changeable During Run — Yes
Minimum — 30.0
Maximum — Upper-Limit (F012)
Units — Hz
F012
)
113