Toshiba W7 DN-57442-006 Installation & Operation Manual page 137

Adjustable speed drives
Table of Contents

Advertisement

Tension Torque Bias Input Selection (Torque Control)
Program  Torque  Torque Control
This parameter Enables/Disables the Tension Torque Bias input function.
When enabled, this parameter identifies the source of the Tension
Torque Bias input signal.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
Load Sharing Gain Input Selection
Program  Torque  Torque Control
This parameter Enables/Disables the Load Sharing Gain input function
and is enabled by selecting a Load Sharing Gain input signal source.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — CN8 Option
6 — Binary/BCD Input
7 — Common Serial (TTL)
8 — RS232/RS485
9 — Communication Card
Forward Speed Limit Input Selection
Program  Torque  Torque Control
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the terminal selected here. If Setting
is selected, the value set at
input.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — Setting (F426)
https://www.toshiba.com/tic/
W7B ASD Installation & Operation Manual
F426
is used as the Forward Speed Limit
Direct Access Parameter Information
Direct Access Number — F423
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F424
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F423-F425