Toshiba W7 DN-57442-006 Installation & Operation Manual page 112

Adjustable speed drives
Table of Contents

Advertisement

F261-F272
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Jog Stop Pattern
Program  Frequency  Jog Settings
This parameter sets the stopping method used while operating in the
Jog mode.
Settings:
0 — Deceleration
1 — Coast
2 — DC Injection
Jump Frequency 1
Program  Special  Jump Frequencies
In conjunction with parameter F271, this parameter establishes a user-
defined frequency range: the Jump Frequency and a plus-or-minus
value. During acceleration, the output frequency of the drive will hold at
the frequency of the lower level of the Jump Frequency range until the
programmed acceleration ramp reaches the upper level of the Jump
Frequency range. Then, the output frequency of the drive will accelerate
to the upper level of the Jump Frequency range and continue upward as
programmed.
During deceleration, the output frequency of the drive will hold at the
frequency of the upper level of the Jump Frequency range until the
programmed deceleration ramp reaches the lower level of the Jump
Frequency range. Then, the output frequency of the drive will decelerate
to the lower level of the Jump Frequency range and continue downward
as programmed.
Once set up and enabled, it is on in all control modes.
User-selected frequencies may be jumped to avoid the negative effects
of mechanical resonance.
Jump Frequency 1 Bandwidth
Program  Special  Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 1
(see F270).
Jump Frequency 2
Program  Special  Jump Frequencies
Same as Jump Frequency 1
frequencies are to be jumped (see the plus-or-minus value setting at
F273). When multiple jump frequencies overlap, the system will
recognize the lowest and the highest frequencies as one jump range.
102
(
F270) and is used when multiple
Direct Access Number — F261
Parameter Type — Selection List
Factory Default — Deceleration
Changeable During Run — Yes
Direct Access Number — F270
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F271
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Direct Access Number — F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
https://www.toshiba.com/tic/

Advertisement

Table of Contents
loading

Table of Contents