Point 2 Setting
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See
F811
for additional information on this setting.
This parameter sets the Communications Reference input value that
represents Communications Reference Speed Setpoint 2 (frequency).
This value is entered as 0 to 100% of the Communications Reference
input value range.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Point 2 Frequency
Program Communications Communication Adjustments
This parameter is used to set the gain and bias of the Communications
Reference speed control input.
See
F811
for additional information on this setting.
This parameter sets the Communications Reference Speed Setpoint 2.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Baud Rate (RS232/RS485)
Program Communications Communication Settings
This parameter sets the RS232/RS485 baud rate.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — 1200
1 — 2400
2 — 4800
3 — 9600
4 — 19200
5 — 38400
RS485 Wire Count
Program Communications Communication Settings
This parameter sets the communications protocol to the 2- or 4-wire
method.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — 2 wire
1 — 4 wire
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F813
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — %
Direct Access Number — F814
Parameter Type — Numerical
Factory Default — 80.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F820
Parameter Type — Selection List
Factory Default — 9600
Changeable During Run — Yes
Direct Access Number — F821
Parameter Type — Selection List
Factory Default — 4 wire
Changeable During Run — Yes
F813-F821
163