S-Pattern Acceleration Upper-Limit Adjustment
Program  Special  ACC/DEC Special
This parameter sets the upper-limit frequency of S-Pattern 1 and 2.
Acceleration/Deceleration Time Lower Limit
Program  Special  ACC/DEC Special
This parameter sets the lower-limit of the Accel/Decel time.
Acceleration Time 3
Program  Special  ACC/DEC 1-4 Settings
This parameter specifies the time for the drive to go from 0.0 Hz to the
Maximum Frequency for the Acceleration 3 profile. The accel/decel
pattern may be set using F502. The minimum accel/decel time may be
set using F508.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the acceleration
time.
Deceleration Time 3
Program  Special  ACC/DEC 1-4 Settings
This parameter specifies the time for the drive to go from the Maximum
Frequency to 0.0 Hz for the Deceleration 3 profile.
The accel/decel pattern may be set using F502. The minimum accel/
decel time may be set using F508.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads.
Automatic Accel/Decel and Stall settings may lengthen the deceleration
time.
Acceleration/Deceleration Pattern 3
Program  Special  ACC/DEC 1-4 Settings
This parameter enables a user-selected preprogrammed output profile
that controls the acceleration and deceleration pattern for the Accel/
Decel 3 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F507
Parameter Type — Numerical
Factory Default — 25.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
Direct Access Number — F508
Parameter Type — Numerical
Factory Default — 0.10
Changeable During Run — Yes
Minimum — 0.01
Maximum — 10.00
Units — Seconds
Direct Access Number — F510
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum —
Maximum — 6000
Units — Seconds
Direct Access Number — F511
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum —
Maximum — 6000
Units — Seconds
Direct Access Number — F512
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
F507-F512
F508
F508
141