Ce Compliance Requirements; Emc Installation Guidelines - Toshiba G7 Quick Start Manual

G7 adjustable speed drive
Hide thumbs Also See for G7:
Table of Contents

Advertisement

Service Life Information
Part Name
Large Capacity Electrolytic
Capacitor
Cooling Fan
CN Connectors
On-board Relays

CE Compliance Requirements

In addition to the local and regional safety requirements, this section describes additional criteria that
must be met to qualify for European Conformity (CE) certification. All relevant apparatus placed on
the European market is required to comply to the European Community directive on electromagnetic
compatibility (EMC). The following instructions provide a means of compliance for the 7-series of
ASDs. A Technical Construction File (TFC) indicates the rationale used to declare compliance and is on
file at Toshiba International Corporation, Houston, Texas U.S.A.

EMC Installation Guidelines

All systems placed on the European market are required to comply with the European Community
directive regarding electromagnet compatibility (EMC). Toshiba ensures that all systems deployed in
the European market have been screened and are in 100% compliance with the following standards:
Radiated Interference: EN 55011 Group 1 Class A
Mains Interference: EN 55011 Group 1 Class A
Radiated Susceptibility: IEC 801-3 1984
Conducted RFI Susceptibility:
Electrostatic Discharge: IEC801-2 1991
Electrical Fast Transient: IEC 801-4 1988
Surge: IEC1000-4-5 1995 2 KV line-to-line, 4 KV line-to-earth
Voltage Interruption: IEC 1000-4-11
General EMC Guidelines for Consideration
Input filters of the appropriate rating shall be used.
Proper grounding is a requirement.
Grounds shall be kept to the minimum length to accomplish the connection.
Grounds shall have low RF impedance.
A central ground shall employed in a complex system.
Paint or corrosion can hamper good grounding; remove as required.
G7 ASD Quick Start Guide
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Service Life
5 Years
26,000 Hours
100 Connects/Disconnects
500,000 Actuations
EN55101-4 (prIEC801-6) Doc 90/30270
pr
Remarks
When not used for long periods,
charge semi-annually.
9