F825-F831
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Send Waiting Time (RS232/RS485) [0.00 = normal]
Program  Communications  Communication Settings
This parameter sets the RS232/RS485 response delay time.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
ASD to ASD Communication (RS232/RS485)
Program  Communications  Communication Settings
In a master/follower configuration, this setting determines the output
parameter of the master ASD that will be used to control the applicable
follower ASDs.
Note:
Select No Follower if
controller. Otherwise, an EOI failure will result.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — Normal (no follower)
1 — Frequency Reference
2 — Output Command Frequency
3 — Torque Command
4 — Output Torque Command
Command Request Disposition on Error
Program  Communications  Communication Error
In the event of a communication error during a transmission, the
command that was transmitted may be cleared or held.
Changes made to this parameter require that the power be cycled (off
then on) for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Input Reference 1
Program  Communications  Scan Receive Settings
Not used.
164
F806
is configured as a Master Output
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
Direct Access Number — F826
Parameter Type — Selection List
Factory Default — Normal (no
follower)
Changeable During Run — Yes
Direct Access Number — F830
Parameter Type — Selection List
Factory Default — Command
Request Cleared
Changeable During Run — Yes
Direct Access Number — F831
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 16