Torque Limit Group
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter is used to
select 1 of 4 preset positive torque limits to apply to the active motor.
The settings of profiles 1 – 4 may be setup at F441, F444, F446, and
F448, respectively.
Settings:
1 — 1
2 — 2
3 — 3
4 — 4
Note:
If using the LCD EOI, press ESC from the Frequency Command
screen to access this parameter.
Feedback in Panel Mode
No path available (Direct Access Only)
While operating using the CN8 Option this parameter Enables/Disables
PID feedback control.
Settings:
1 — Enabled
2 — Disabled
Note:
If using the LCD EOI, press ESC from the Frequency Command
screen to access this parameter.
CN8 Option Override Multiplication Gain
Program  Feedback  Override Control
If operating using the CN8 Option this parameter provides a value to be
used in the event that Setting is selected for the Frequency Override
Multiplying Input (F661).
Low Output Disable Control and Stopping Method
Program  Special  Low Output Disable Function
Enables/Disables the Low Output Disable function and, if enabled,
selects a stopping method.
Settings:
0 — Disabled
1 — Enabled — Decel Stop
2 — Enabled — Coast Stop
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F723
Parameter Type — Selection List
Factory Default — 1
Changeable During Run — Yes
Direct Access Number — F724
Parameter Type — Selection List
Factory Default — Enabled
Changeable During Run — Yes
Direct Access Number — F729
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — -100.00
Maximum — 100.00
Direct Access Number — F731
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
F723-F731
157