Toshiba W7 DN-57442-006 Installation & Operation Manual page 160

Adjustable speed drives
Table of Contents

Advertisement

F641-F651
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Earth Fault Alarm Time
Program  Special  Earth Fault
In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm
is activated.
This parameter sets the start-time of the count-down timer.
Earth Fault Trip Level
Program  Special  Earth Fault
This parameter sets the threshold level (%) that must be exceeded to
meet the Earth Fault Trip activation criteria.
Earth Fault Trip Time
Program  Special  Earth Fault
In the event that the Earth Fault Trip activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Trip is
activated.
This parameter sets the start-time of the count-down timer.
Acceleration/Deceleration Frequency Adjustment
Program Terminal  Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Base Frequency. When enabled, either VI/II or RR
may be used as an input source for the modification of the Base
Frequency setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Upper Limit Frequency Adjustment
Program Terminal  Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Upper-Limit. When enabled, either VI/II or RR may be
used as an input source for the modification of the Upper-Limit setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
150
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 0.00
Maximum — 100
Units — %
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F650
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes