Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Earth Fault Alarm Time
Program Special Earth Fault
In the event that the Earth Fault Alarm activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Alarm
is activated.
This parameter sets the start-time of the count-down timer.
Earth Fault Trip Level
Program Special Earth Fault
This parameter sets the threshold level (%) that must be exceeded to
meet the Earth Fault Trip activation criteria.
Earth Fault Trip Time
Program Special Earth Fault
In the event that the Earth Fault Trip activation criteria is met, a timer
begins to count down to zero. Upon reaching zero, the Earth Fault Trip is
activated.
This parameter sets the start-time of the count-down timer.
Acceleration/Deceleration Frequency Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Base Frequency. When enabled, either VI/II or RR
may be used as an input source for the modification of the Base
Frequency setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
Upper Limit Frequency Adjustment
Program Terminal Analog Input Functions
This parameter Enables/Disables the feature that allows for the external
adjustment of the Upper-Limit. When enabled, either VI/II or RR may be
used as an input source for the modification of the Upper-Limit setting.
Settings:
0 — Disabled
1 — VI/II
2 — RR
150
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F642
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 0.00
Maximum — 100
Units — %
Direct Access Number — F643
Parameter Type — Numerical
Factory Default — 1.00
Changeable During Run — No
Minimum — 0.00
Maximum — 2.50
Units — Seconds
Direct Access Number — F650
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F651
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes