Toshiba W7 DN-57442-006 Installation & Operation Manual page 153

Adjustable speed drives
Table of Contents

Advertisement

Pattern Run (Not Used)
N/A
The Pattern Run function is not supported with the W7B ASD.
Motor Overload Protection Level 1
Program  Motor  Motor Set 1
The Motor Overload Protection Level 1 parameter specifies the motor
overload current level for motor set 1. This value is entered as either a
percentage of the full load rating of the ASD or as the FLA of the motor.
The unit of measurement for this parameter may be set to Amps or it
may be set as a percentage of the ASD rating. The name-plated FLA of
the motor may be entered directly when Amps is selected as the unit of
measurement (see
F701
to change the display unit).
Motor Overload Protection Level settings (1 – 4) will be displayed in
Amps if the EOI display attributes are set to V/A rather than %.
Note:
Not used with the W7B ASD.
Stall Prevention Level
Program  Protection  Stall
This parameter specifies the output current level at which the output
frequency is reduced in an attempt to prevent a trip. The over-current
level is entered as a percentage of the maximum rating of the drive.
Note:
Parameter
F017
(Soft Stall) must be enabled to use this
feature.
ASD Trip Record Retention Selection
Program  Protection  Trip Settings
This parameter Enables/Disables the Trip Save at Power Down setting.
When enabled, this feature logs the trip event and retains the trip
information when the system powers down. The trip information may be
viewed from the Monitor screen.
When disabled, the trip information will be cleared when the system
powers down.
Settings:
0 — Cleared after power off
1 — Hold after power off
https://www.toshiba.com/tic/
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Direct Access Number — F520
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Direct Access Number — F600
Parameter Type — Numerical
Factory Default — 100.0
Changeable During Run — Yes
Minimum — 10.0
Maximum — 100.0
Units — %
Direct Access Number — F601
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During Run — Yes
Minimum — 0.00
Maximum — 200.0
Units — %
Direct Access Number — F602
Parameter Type — Selection List
Factory Default — Cleared after
power off
Changeable During Run — No
F520-F602
143