Toshiba W7 DN-57442-006 Installation & Operation Manual page 140

Adjustable speed drives
Table of Contents

Advertisement

F440-F444
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
Power Running Torque Limit 1
Program  Torque  Torque Limit Settings
This parameter determines the source of the control signal for the
positive torque limit setting. If Setting is selected, the value set at
used as the Power Running Torque Limit 1 input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F441)
Power Running Torque Limit 1 Level [250% = disabled]
Program  Torque  Manual Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if Setting is selected at F440. This value provides the positive
torque upper-limit for the 1 motor.
Regenerative Braking Torque Limit 1
Program  Torque  Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2 (Option Card)
5 — Setting (F443)
Regenerative Braking Torque Limit 1 Level [250% = disabled]
Program  Torque  Manual Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque
Limit 1 if Setting is selected at F442.
Power Running Torque Limit 2 Level [250% = disabled]
Program  Torque  Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 2
motor profile when multiple motors are controlled by a single drive or
when a single motor is controlled by multiple profiles.
130
Direct Access Number — F440
Parameter Type — Selection List
Factory Default — Setting (F441)
F441
is
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — Setting (F443)
F443
is used for this
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %