Toshiba W7 DN-57442-006 Installation & Operation Manual page 150

Adjustable speed drives
Table of Contents

Advertisement

F503-F506
Direct Access Parameter Information
W7B ASD Installation & Operation Manual
S-Curve Acceleration/Deceleration Pattern 2
Program  Special  ACC/DEC 1-4 Settings
This parameter enables a user-selected preprogrammed output profile
that controls the acceleration and deceleration pattern for the Accel/
Decel 2 parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Acceleration/Deceleration Pattern 1-4 Selection
Program  Special  ACC/DEC 1-4 Settings
While operating using the CN8 Option this parameter selects the accel/
decel profile to be used during a multiple-accel/decel profile
configuration. The accel/decel setting for selections 1 – 4 may be found
at F009, F500, F510, and F514, respectively.
Settings:
1 — Acc/Dec 1
2 — Acc/Dec 2
3 — Acc/Dec 3
4 — Acc/Dec 4
Note:
If using the LCD EOI, press ESC from the Frequency Command
screen to access this parameter.
Acceleration/Deceleration Switching Frequency 1
Program  Special  ACC/DEC Special
This parameter sets the frequency at which the acceleration control is
switched from the Accel 1 profile to the Accel 2 profile during a multiple-
acceleration profile configuration.
S-Pattern Acceleration Lower-Limit Adjustment
Program  Special  ACC/DEC Special
This parameter sets the lower-limit of S-Pattern 1 and 2.
140
Direct Access Number — F503
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F504
Parameter Type — Selection List
Factory Default — Acc/Dec 1
Changeable During Run — Yes
Direct Access Number — F505
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F506
Parameter Type — Numerical
Factory Default — 25.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 50.00
Units — %
https://www.toshiba.com/tic/

Advertisement

Table of Contents
loading

Table of Contents