HMI as Feedback of the local push button operations
As consequence of the operations described in the apposite section, when the Z or S buttons are released, the feedback of the
executed operation is displayed in the bottom of the LCD see the example below with one of the following strings:
Message
! Oper Done
! Proc Too Low
! Proc Too High
! New URV Error
! Span Error
! Oper Disabled
Description
The push button operation has been successfully executed
The Pressure measured in input is too low and not acceptable for the requested operation
The Pressure measured in input is too high and not acceptable for the requested operation
The Zero (Z) operation cannot be accepted because the URV would be shifted outside the Upper Sensor limit
The Span (S) operation cannot be accepted because the new URV would be too close to the LRV and their difference lower
than the Minimum Span value
The push button operation has been refused because the Write Protection is enabled with the hardware button or in PB_
WRITE_LOCKING or because the Local Operation is disabled in the PB_LOCAL_OP_ENA