2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
Idx
Parameter
0
BLOCK_OBJ
1
ST_REV
2
TAG_DESC
3
STRATEGY
4
ALERT_KEY
TARGET
ACTUAL
5
MODE_BLK
PERMITTED
NORMAL
6
BLOCK_ERR
7
UPDATE_EVT
8
BLOCK_ALM
9
TRANSDUCER_DIRECTORY
10
TRANSDUCER_TYPE
11
TRANSDUCER_TYPE_VERSION The version of the transducer identified by TRANSDUCER_TYPE in the form 0xAABB where AA is the major revision
12
XD_ERROR
13
COLLECTION_DIRECTORY
14
HMI_CONTRAST
15
HMI_LANGUAGE
16
HMI_MODE
17
HMI_SW_REV
18
HMI_LIN_TYPE
Description / Range / Selections / Notes
In the Block Object data structure, there are different items describing the block characteristics. Execution period,
Number of parameters in the block, the DD Revision, Profile Revision, View Objects characteristics and so on
The revision level of the Static data associated with the Function Block. The revision level is incremented each time a
static parameter value (S – under Storage) in the block is changed.
The user description of the intended application of the block
The strategy field can be used to identify grouping of blocks. This data is not checked or processed by the block.
The identification number of the plant unit. This information may be used in the host for sorting alarms, etc.
AUTO / OOS
AUTO / OOS
AUTO
This parameter reflects the error status associated with the hardware or software components associated with a
block. It is a bit string, so that multiple errors may be shown.
Bit 15 = Out of Service
This alert is generated by any change to the static data
The block alarm is used for all configuration, hardware, and connection failure or system problems in the block. The
cause of the alert is entered in the sub-code field. The first alert to become active will set the Active Status in the
status parameter. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be
reported without clearing the Active Status, if the sub-code has changed.
Directory that specifies the number and starting indices of the transducers in the transducer block
Identifies the transducer type.
of the transducer specification on which the transducer is based, and BB is a revision number assigned and
controlled by the manufacturer of the device.
Transducer block error sub-code
Directory that specifies the number, starting indices, and the DD items IDs of the data collections in each transducer
within a tb
Display Contrast 0 ....100 [50]
0:
English (default)
1:
German
2
French
3
Spanish
4:
Italian
5:
One Line
6:
One Line with Bargraph (default)
9:
Two Lines
10:
Two Lines with Bargraph
0
Not Installed
xxx
Display SW Revision
0:
Linear (default)
1:
Square root
2:
SQRT 3° pow
3:
SQRT 5° pow
4:
Cylindrical lying container
5:
Spherical container
6:
Bidirectional Flow
The selectable modes by the operator.
The mode the block is currently in.
The allowed modes the operator can select as Target
The common mode for the Actual.
The MODE_BLK_ACTUAL = Out of Service.
Active only if one of the 4 HMI_Variable_x is set to HMI_Variable.
In this case the PRTB_PRIMARY_VALUE is calculated with the selected HMI_
LIN_TYPE and the result ready to be scaled with the HMI_VARIABLE_RANGE.
71