Special operations
Savings
In order to keep a valid device setting to be used as reference when a valid condition has to be recovered in case of wrong
operations, it is possible save all the above calibrations as Factory or User calibrations and the complete device configuration.
The possible savings are the following and are executed in two steps:
1 Selecting and writing the proper save operation in the RB_SPECIAL_OPERATION
2 Selecting and writing in the RB_RESTART = Special Operations
Save Configuration as Default
Save P-dP Trimming as Factory
Save Static P Trimming as Factory
Save Sensor Temp Trimming as Factory
Save P-dP Trimming as User
Save Static P Trimming as User
Save Sensor Temp Trimming as User
Resets
The transmitter offers some reset operations executed in two steps:
1 Selecting and writing the proper reset code in the RB_SPECIAL_OPERATION
2 Selecting and writing in the RB_RESTART = Special Operations
Reset Configuration to Default Values
Reset P-dP Trimming to Factory
Reset Static P Trimming to Factory
Reset Sensor Temp Trimming to Factory
Reset P-dP Trimming to User
Reset Static P Trimming to User
Reset Sensor Temp Trimming to User
When this operation is executed, the complete device configuration is saved as default configuration at
which the device returns when the Reset to Default configuration is executed. After the device has been
properly configured, the user can decide to save it as a default configuration in order to recover it if
necessary
The P-dP Sensor calibration/trimming is saved as Factory Calibration. This operation is typically executed in
the Factory after the Sensor has been calibrated to the customer's specified measuring range or, in case the
customer didn't requested any measuring range, at the maximum sensor range
The Static P Sensor calibration/trimming is saved as Factory Calibration.
The Sensor Temp. calibration/trimming is saved as Factory Calibration
The P-dP Sensor calibration/trimming is saved as User Calibration. This operation is typically executed by
the user after the Sensor has been calibrated at the desired measuring range.
The Static P Sensor calibration/trimming is saved as User Calibration
The Sensor Temp. calibration/trimming is saved as User Calibration
When this operation is executed, the complete device configuration returns to the configuration
previously saved as default configuration.
Return the P-dP Sensor calibration/trimming at the calibration previously saved as Factory Calibration
Return the Static Pressure Sensor calibration/trimming at the calibration previously saved as Factory
Calibration
Return the Sensor temperature calibration/trimming at the calibration previously saved as Factory
Calibration
Return the P-dP Sensor calibration/trimming at the calibration previously saved as User Calibration.
Return the Static Pressure Sensor calibration/trimming at the calibration previously saved as User
Calibration
Return the Sensor temperature calibration/trimming at the calibration previously saved as User
Calibration