ABB 2600T Series Instruction Manual page 61

266 with foundation fieldbus communication
Table of Contents

Advertisement

2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
Idx
Parameter
45
STATIC_P_CAL_POINT_LO
46
STATIC_P_CAL_MIN_SPAN
47
STATIC_P_CAL_UNIT
48
STATIC_P_TRIM_VALUE
49
DESIDERED_STATIC_P_VALUE
50
RESET_STATIC_P_BIAS
51
STATIC_P_BIAS_VALUE
52
MAX_WORKING_PRESSURE
53
SENSOR_TEMP_CAL_POINT
54
SET_UPPER_RANGE_POINT_PV SPAN Button emulation for Process Value
55
SET_LOWER_RANGE_POINT_PV ZERO Button emulation for Process Value.
56
PARALLEL_SHIFT_PV
57
MODULE_TYPE
SENSOR_O_RING_MATERIAL_
58
HSP
PROCESS_CONNECTION_TYPE_
59
HSP
PROCESS_CONNECT_
60
MATERIAL_HSP
61
DRAIN_VENT_MATERIAL_HSP
SENSOR_O_RING_MATERIAL_
62
LSP
PROCESS_CONNECTION_TYPE_
63
LSP
PROCESS_CONNECT _
64
MATERIAL_LSP
65
DRAIN_VENT_MATERIAL_LSP
GAUGE_ABS_PROC_CONNECT_
66
MTL
67
REMOTE_SEALS_TYPE_HSP
REMOTE_SEALS_FILL_FLUID_
68
HSP
REMOTE_SEALS_ISOLATOR_
69
HSP
70
REMOTE_SEALS_TYPE_LSP
REMOTE_SEALS_FILL_FLUID_
71
LSP
REMOTE_SEALS_ISOLATOR_
72
LSP
Description / Range / Selections / Notes
Static Pressure Calibration point Low expressed in STATIC_P_CAL_UNIT
Expressed in STATIC_P_CAL_UNIT.
Static Pressure Calibration Only Pressure Units are allowed
Static Pressure Value after the Calibration. Reference value to be adjusted with the calibration operations
Expressed in TERTIARY_VALUE_RANGE.Unit
Reset BIAS_VALUE to 0.0 so that  TERTIARY_VALUE = STATIC_P_TRIM_VALUE
Expressed in TERTIARY_VALUE_RANGE.Unit
Expressed in TERTIARY_VALUE_RANGE Unit
Expressed in SECONDARY_VALUE_RANGE.Unit
The PRIMARY_VALUE_RANGE is shifted to produce the
desired percentage in output.
Type of Transducer technology (piezo, inductive, capacitive)
Sensor O-Ring Material
Process connection type
Process connection material
Drain vent Material
Sensor O-Ring Material
Process connection type
Process connection material
Drain vent Material
Process connection material for Gauge or Absolute sensor types
Remote Seal type
Remote Seal Fill Fluid
Remote Seal Isolator
Remote Seal type
Remote Seal Fill Fluid
Remote Seal Isolator
Static Pressure Sensor Calibration minimum Span value.
When calibration is done, the two calibrated points (high
and low) must not be too close together.
Force the Measured Static Pressure to a selected Value
setting an offset between Measured and Process value. 
TERTIARY_VALUE = STATIC_P_TRIM_VALUE +/-
STATIC_P_BIAS_VALUE
Read the offset between Measured and Process values 
STATIC_P_BIAS_VALUE = STATIC_P TRIM_VALUE –
TERTIARY_VALUE
Max Sensor Working Pressure
Sensor Temperature Calibration Point
An adjustment of the sensor temperature is effected by
writing the correct temperature value. This setting has no
influence to the accuracy of the pressure measurement
The instant measured value is written to PRIMARY_VALUE_
RANGE_100%
The instant measured value is written to PRIMARY_VALUE_
RANGE_0%
The PRIMARY_VALUE_RANGE span remains unchanged.
See dedicated section
High Side
Low Side
High Side
Low Side
61