ABB 2600T Series Instruction Manual page 92

266 with foundation fieldbus communication
Table of Contents

Advertisement

92
2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
. . .Block Mapping
Idx Parameter
Description / Range / Selections / Note
Expressed in OUT_SCALE Unit
33
ROUT_IN
Used when the mode is ROUT.
34
SHED_OPT
Define actions to be taken on remote control device timeout
Expressed in PV_SCALE Unit.
35
RCAS_OUT
Used when mode is RCAS.
Expressed in OUT_SCALE Unit.
36
ROUT_OUT
Used when mode is ROUT.
The high and low scale values, engineering units code, and number of digits to the right of the decimal point, associated with
37
TRK_SCALE
TRK_VAL.
This discrete input is used to initiate external tracking of the block output to the value specified by TRK_VAL.
38
TRK_IN_D
39
TRK_VAL
Expressed in TRK_SCALE Unit.
Expressed in FF_SCALE Unit.
40
FF_VAL
The high and low scale values, engineering units code, and number of digits to the right of the decimal point associated with FF_
41
FF_SCALE
VAL
The gain that the feed forward inpt is multiplied by before it is added to the calculated control output.
42
FF_GAIN
This alert is generated by any change to the static data
43
UPDATE_EVT
The block alarm is used for all configuration, hardware, connection failure or system problems in the block. The cause of the alert
is entered in the subcode field. The first alert to become active will set the Active Status in the status parameter. As soon as the
44
BLOCK_ALM
Unreported status is cleared by the alert reporting task, another block alert may be reported without clearing the Active Status, if
the subcode has changed
The summary alarm is used for all process alarm in the block. The cause of the alert is entered in the subcode field. The first alert
45
ALARM_SUM
to become active will set the Active Status in the status parameter. As soon as the Unreported status is cleared by the alert
reporting task, another block alert may be reported without clearing the Actve Status, if the subcode has changed.
46
ACK_OPTION
Used to set auto acknowledgment of the alarms
Alarm Hysteresis is the amount the PV
47
ALARM_HYS
must return within the alarm limit before
the alarm condition clears.
48
HI_HI_PRI
0 - 15
Critical Limit High producing the High-
49
HI_HI_LIM
High Alarm
50
HI_PRI
0 - 15
Advisory Limit High producing the High
51
HI_LIM
Alarm
52
LO_PRI
0 - 15
Advisory Limit Low producing the Low
53
LO_LIM
Alarm
54
LO_LO_PRI
0 – 15
Critical Limit Low producing the Low-Low
55
LO_LO_LIM
Alarm
56
DV_HI_PRI
0 - 15
Deviation High Limit producing the
57
DV_HI_LIM
Deviation High Alarm
58
DV_LO_PRI
0 - 15
Deviation Low Limit producing the
59
DV_LO_LIM
Deviation Low Alarm
60
HI_HI_ALM
High-High Alarm
61
HI_ALM
High Alarm
62
LO_ALM
Low Alarm
63
LO_LO_ALM
Low-Low Alarm
64
DV_HI_ALM
Deviation High Alarm
65
DV_LO_ALM
Deviation Low Alarm
66
T1_RATE
Derivative 1st order filter
67
BETA
Set-point weight proportional part
61
GAMMA
Set-point weight derivative part
Target output value provided by a supervisory host
Block setpoint Value after ramping – provided by a supervisory host for back
calculations and to allow action to be taken under limiting conditions or mode change
Block output Value provided to a supervisory host for a back calculation to allow
action to be taken under limiting conditions or mode change
This input is used as the track value when external tracking is enabled by TRK_IN_D.
The feed forward value and status
0 or > 0 expressed as percent of the OUT_SCALE span (default =[0.5%])
Expressed in OUT_SCALE unit.