ABB 2600T Series Instruction Manual page 102

266 with foundation fieldbus communication
Table of Contents

Advertisement

102
2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
Diagnostic
Block_Err
Possible Reasons
SELECT_TYPE = 0 (uninitialized)
Block Configuration error
Input Failure/process
SELECT_TYPE = AVERAGE and at least one IN is BAD
variable has BAD status
Out-of-Service
The Actual_Mode is OUT OF SERVICE
NOTE A:
The specific block cannot be switched out from OUT OF SERVICE due to the Configuration Error. The Bad-
Configuration Error Status is overridden by the Bad-Out Of Service Status.
OUT Status
When in AUTO mode the OUT reflects the Value and Status of the selected input (IN_x).
If there are no inputs used, or the number of inputs with GOOD status is less than the MIN_GOOD value, the OUT status shall be
BAD-Non Specific.
The SELECTED output shall have Good(NC) status, unless the block is out of service.
With the STATUS_OPTS it is possible selects the following options:
• Use Uncertain as Good: Set the IS_OUT status to Good when the Selected Input Status is Uncertain
• Uncertain if Manual Mode: The Status of the IS_OUT is set to Uncertain when the Mode is set to Manual
Troubleshooting
Problem
The Block cannot be removed
from OOS mode
The OUT Status is BAD
The OUT Status has the Limit
bits (0, 1) set to Constant
Block Alarm Not Working
(Events not notified)
Possible cause
The Target Mode is not set to AUTO
The Configuration Error bit is set in the
BLOCK_ERR
The RESOURCE BLOCK is not in AUTO mode
The Block is not scheduled
All the Inputs have a BAD status
The number of inputs with GOOD status is less
than the MIN_GOOD value
The OP_SELECT is different by 0 and force in
output and Input with BAD status
The SELECT_TYPE = AVERAGE and at least
one Input has Status BAD
The Actual Mode is set to MAN
The FEATURE_SEL has not the Reports bit Set
OUT Status
BAD + Out Of Service
See Note A
BAD + non specific
BAD + Out Of Service
Solution
Set the Target Mode to AUTO and/or remove the OOS
Set the SELECT_TYPE with a valid value. It must be different by 0
and in the range 1 – 5
Set the Target Mode of the RESOURCE BLOCK to AUTO mode
Design the FB Application correctly and download it to the
devices
Check the upstream blocks
Set the Target Mode to AUTO
Set the REPORTS bit in the FEATURE_SEL of the RESOURCE
BLOCK