ABB 2600T Series Instruction Manual page 78

266 with foundation fieldbus communication
Table of Contents

Advertisement

2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
78
. . .Diagnostic, BlOCK_ERR and Status Byte
Cat .
Error
Process errors
High
Range
Primary
Variable Out
of Range
Low
Range
PILD
Affect
PV = 0
PILD Output
PILD
Affect
PV = 1
PILD
Affect
PILD
PV = 0
Changed
Operating
PILD
Conditions
Affect
PV = 1
Out Of Service
Device Troubleshooting
Cat
Error
HMI code
Electronics errors
Memory Failure
Electronic Interface
error.
Non-Volatile memory
burn error
Pressure sensor errors
Missing
Primary
Signal
Sensor
Invalid
Invalid
Sensor
Sensor Memory Fail
P-dP Sensor Fail
Static Pressure Sensor
Fail
Block err
HMI code
PRTB.Other
S050.010
ADTB.Device
Needs
M018.038
Maintenance Soon
ADTB.Device
Needs
M018.038
Maintenance Soon
PRTB.Out of
Service
Description
The device data loaded at the start
F116.023
up are corrupted precluding the
correct functionality of the device
Exchange of data between
M030.020
Electronics and Sensor have
problems
The device continue to work without
problems but at the next power
M026.024
cycle the new configuration will be
lost
The primary signal of the sensor is
no longer available. The transducer
is not in a condition to generate a
valid signal.
F120.016
Sensor and/or the connected
electronics are incompatible
The data in the sensor memory are
F118.017
corrupted precluding the correct
functionality of the device
The sensor signal value is incorrect
F114.003
due to a mechanical failure
The sensor signal value is incorrect
due to a mechanical failure. Valid
F112.001
only for Differential pressure
models
PRTB_x_VALUE Status
PRIMARY
SECONDARY
TERTIARY
GOOD_NC Non Specific No Limit
GOOD_NC Non Specific No Limit
BAD Sensor
GOOD_NC Non
Failure No
Specific No
BAD Sensor Failure No Limit
Limit
Limit
GOOD_NC Non Specific No Limit
BAD Sensor
GOOD_NC Non
Failure No
Specific No
BAD Sensor Failure No Limit
Limit
Limit
BAD Out of Service
Possible Cause
Electronic memory corrupted
Exchange of non-critical data
between sensor and electronics is
precluded due to problem in the
transmitter circuit of the electronics
or in receiver circuit of the sensor
Writings to the electronic non-
Volatile Memory was not successful
The sensor signal is not being
updated correctly as a result of an
electronics failure, sensor error or a
poorly connected sensor cable.
The sensor model/version is not
longer compatible with the
connected electronic version
Sensor memory corrupted
Mechanical damage to the sensor.
Loss of fill fluid from the cell;
ruptured diaphragm, broken
sensor....
The circuitry for the sampling of the
static pressure has failed.
QUATERNARY
PDP_TRIM
SP_TRIM
UNCERTAIN
engineering unit
range violation
High Limit
GOOD_NC Non Specific No
Limit
UNCERTAIN
engineering unit
range violation
Low Limit
Suggested Actions
The electronics must be replaced
Power cycle the device and retry the
operation, if the error persist the
electronics should be replaced
The electronics should be replaced
as soon as possible.
Check cable connection, check
sensor and if problem persists, the
sensor must be replaced.
The sensor must be replaced
The Sensor must be replaced
The Sensor must be replaced
The Sensor must be replaced