Set the LRV by Local Keys

When the a pplied pressure is stable push the
Zero local adjustment key (Z) lo cated on th e
terminal block and rel ease. After this operation
the reading shall move to 4 mA. If n o changes
occur repeat the operation.

Set the LRV by Digital LCD Integral Display

To set the LRV reading of the Digital LCD Integral Display (the engineering units have to be selected):
Navigate the Digital LCD Integral Display menu, select
the Zero values will be available.
Select the desired value and confirm.
Digital LCD Integral Display Keys sequence to set the Display LRV : 3 – 7 – 2 - Edit
To set the Transmitter LRV without reference pressure:
Navigate the Digital LCD Integral Display menu, select
Set
LRV, and the LRV values will be available. To modify select
in reverse color with the up and down keys and confirm with
and confirm with
OK.
Note: the minimum and the maximum values to select are indicated on the display.
Digital LCD Integral Display Keys sequence to set the LRV wihout pressure: 2 – 1 – 2 – 2 – Edit
To set the Transmitter LRV with reference pressure:
Set the transmitter applie d pressure as for Lower Range value (0%). Navigate the Digital LCD Integral
Device Config
Display menu, select
Select
to start the autoadjust.
OK
Digital LCD Integral Display Keys sequence to set the LRV wih pressure: 2 – 1 – 1 – 1 – OK

Set the LRV by CoMeter

LRV configuration by CoMeter is available with the 695 Field Indicator. Please refer to the device manual for
the appropriate operations.

Set the LRV by HHT

LRV configuration by Hand Held Terminal is available. Please refer to the device manual for the appropriate
operations.

Set the LRV by PC

LRV configuration by PC i s available using dedicated Software. ABB can provi de the references and the
Software. Please refer to the Software instructions for the appropriate operations.

Set the URV

When a URV different from the selected is needed it is possible to cha nge it following one of the methods
described in the next paragraphs.
Display
Device Config
>
>
Rerange
Rerange with pressure
364Ax-Gx Instruction Manual
>
>
Display settings
>
Rerange
>
Edit
then scroll the desired value for the digit
Next.
Repeat the operation for the seven digits
>
Set LRV
(0%), and
Display LRV
Rerange no pressure
(0%).
26
>