2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
Idx
Parameter
43
CB_HW_REV
44
CAPABILITY_LEV
45
COMPATIBILITY_REV
46
FD_VER
47
FD_FAIL_ACTIVE
48
FD_OFFSPEC_ACTIVE
49
FD_MAINT_ACTIVE
50
FD_CHECK_ACTIVE
51
FD_FAIL_MAP
52
FD_OFFSPEC_MAP
53
FD_MAINT_MAP
54
FD_CHECK_MAP
55
FD_FAIL_MASK
56
FD_OFFSPEC_MASK
57
FD_MAINT_MASK
58
FD_CHECK_MASK
59
FD_FAIL_ALM
60
FD_OFFSPEC_ALM
61
FD_MAINT_ALM
62
FD_CHECK_ALM
63
FD_FAIL_PRI
64
FD_OFFSPEC_PRI
65
FD_MAINT_PRI
66
FD_CHECK_PRI
67
FD_SIMULATE
68
FD_RECOMMEN_ACT
69
EXTENDED_ACTIVE
70
DIAGNOSIS_HISTORY
Description / Range / Selections / Notes
"XX.YY.ZZ" (01.00.00)
Not Supported
0x01
Indicates value of major version of instrument diagnostics specifications (FF-912).
Active error conditions mapped as Failure
Active error conditions mapped as Out of Specification
Active error conditions mapped as Maintenance
Active error conditions mapped as Check Function
Errors Mapped as Failure
Errors Mapped as Out of Spec
Errors Mapped as Maintenance:
Errors Mapped as Check Function
Fail error to be masked
Out of Spec errors to be masked
Maintenance errors to be masked
Function Check errors to be masked
Fail Alarm Object
Out of Spec Alarm Object
Maintenance Alarm Object
Function Check Alarm Object
Fail error priority
Out of Spec error priority
Maintenance error priority
Function Check error priority
1: Disabled
Default
2: Active
Numeric Code defining the corrective action to be taken for the problem solution. When the Device's DD has been
imported in the Hosts it converts the numeric code into a Textual info comprehensible for the user
Some of the Active Errors of Fail, Maint, Out of Spec, Function Check classification could be produced by more root
causes that can be seen by reading this parameter. SEE its bit MAPPING DETAIL in the dedicated section
The bit associated at each error condition is permanently set after the condition became set at least one time Its bit
mapping is the same as for x_ACTIVE. SEE its bit MAPPING DETAIL in the dedicated section
According to the NAMUR NE107 Categories.
Bit = 0 – No Error active
Bit = 1 – Error active
It is bit string, and multiple conditions may be shown.
SEE its bit MAPPING DETAIL in the dedicated section
Default mapping:
Bit 1 Static Pressure Sensor failure
Bit 2 Sensor Temperature failure
Bit 3 Pressure or Diff.Pressure Sensor failure
Bit 4 Pressure or Diff.Pressure Out of Sensor limits
Bit 5 Static Pressure Out of Sensor Limits
Bit 11 Pressure Over-range
Bit 12 Sensor Signal not Valid
Bit 14 Sensor memory fail
Bit 17 Electronic memory fail
Default mapping:
Bit 6 Sensor Temperature Out of the Operating Limits
Bit 10 Primary Variable Out of Range
Default Mapping:
Bit 7 Replace operation required
Bit 8 PILD output condition detected
Bit 9 PILD operating condition has changed. New PILD
training is required
Bit 14 Sensor Non-Volatile memory write error
Bit 15 Electronic Interface error with the connected sensor
Bit 17 Electronic Non-Volatile memory write error
Bit 19 Max.Working pressure limit has been exceeded
Default Mapping:
Bit 0 Function Check
Bit 18 Input simulation active
Default no error masked
The simulation can be enabled only if the SW4 of the
electronics is in moved to Simul Mode = ON (1) position
53