2 6 0 0 T S E R I E S | P R E S S U R E T R A N S M I T T E R S | O I/ 2 6 6/ F F - E N R E V. E
Device Diagnostic
The 266 PdP FF produces different type of diagnostic information:
• Device Diagnostic
These are the diagnostic information produced by the Resource and Transducer Blocks and refer to the device status/health
• Process Diagnostic
These are the diagnostic information which are seen through process variable status and process alarms such as the HI, HI HI,
LO, LO LO, DV HI and DV LO alarms implemented in various Function blocks.
Scope of this section is to describe the Device Diagnostic to be consumed in the Asset Management Software.
Standard errors
The FF standard parameter defining the device diagnostic conditions is the BLOCK_ERR contained by each block and mapped as
follow:
BLOCK_ERR mapping
Bit 0
Other
Bit 1
Block Configuration Error
Bit 2
Link Configuration Error
Bit 3
Simulate Active
Bit 4
Local Override
Bit 5
Device Fault State Set
Bit 6
Device Needs Maintenance Soon
Bit 7
Sensor Failure detected by this block/process variable has a status of BAD, Sensor Failure
Bit 8
Output Failure detected by this block/backcalculation input has a status of BAD, Device Failure
Bit 9
Memory Failure
Bit 10
Lost Static Data
Bit 11
Lost NV Data
Bit 12
Readback Check Failed
Bit 13
Device Needs Maintenance Now
Bit 14
Power Up
Bit 15
Out of Service