ABB typically configures 266 pressure transmitters according
to the user requirements. A typical configuration includes:
• TAG number
• Calibrated span
• Output linearization
• LCD display configuration
Hazardous area considerations
The transmitter must be installed in hazardous area only if it is
properly certified. The certification plate is permanently fixed
on the neck of the transmitter top housing. The 266 Pressure
Transmitter Line can have the following certifications:
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T6...T4 Ga, II 1/2 G Ex ia IIC T6...T4 Ga/Gb,
II 1 D Ex ia IIIC T85 °C Da, II 1/2 D Ex ia IIIC T85 °C Da;
IP66, IP67.
• IECEx (code E8) approval
Ex ia IIC T6...T4 Ga/Gb, Ex ia IIIC T85 °C Da; IP66, IP67.
EXPLOSION PROOF:
• ATEX Europe (code E2) approval
II 1/2 G Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
II 1/2 D Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C;
IP66, IP67.
• IECEx (code E9) approval
Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C; IP66, IP67.
FM Approvals US (code E6), FM Approvals Canada (code E4):
• Explosionproof (US): Class I, Division 1,
Groups A, B, C, D; T5
• Explosionproof (Canada): Class I, Division 1,
Groups B, C, D; T5
• Dust-ignitionproof: Class II, Division 1, Groups E, F, G;
Class III, Div. 1; T5
• Flameproof (US): Class I, Zone 1 AEx d IIC T4 Gb
• Flameproof (Canada): Class I, Zone 1 Ex d IIC T4 Gb
• Nonincendive: Class I, Division 2, Groups A, B, C, D T6...T4
• Energy limited (US): Class I, Zone 2 AEx nC IIC T6...T4
• Energy limited (Canada): Class I, Zone 2 Ex nC IIC T6...T4
• Intrinsically safe: Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G T6...T4
Class I, Zone 0 AEx ia IIC T6...T4 (US)
Class I, Zone 0 Ex ia IIC T6...T4 (Canada)
Type 4X, IP66, IP67 for all above markings.
COMBINED FM Approvals US and Canada
• Intrinsically safe (code EA)
COMBINED ATEX, FM and IECEx Approvals (code EN)
Technical Regulations Customs Union EAC (Russia,
Kazakhstan, Belarus), Inmetro (Brazil), Kosha (Korea)
NEPSI China approvals:
• INTRINSIC SAFETY Ex ia (code EY):
Ex ia IIC T4/T5/T6 Ga, Ex ia IIC T4/T5/T6 Ga/Gb,
Ex iaD 20 T85/T100/T135, Ex iaD 20/21 T85/T100/T135.
• EXPLOSION PROOF (code EZ):
Ex d IIC T6 Gb, Ex tD A21 IP67 T85 °C.
• INTRINSIC SAFETY Ex ic (code ES):
Ex ic IIC T4~T6 Gc, Ex nA IIC T4~T6 Gc,
Ex tD A22 IP67 T85 °C.
IMPORTANT
REFER TO CERTIFICATES FOR AMBIENT TEMPERATURE
RANGES RELATED TO THE DIFFERENT TEMPERATURE
CLASSES.
HIGH STATIC VERSION IS NOT IN COMPLIANCE WITH ISA
12.27.01 FOR SEALING REQUIREMENTS, SPECIFICALLY FOR
FM APPROVAL (Canada).
WARNING
General Risk for model 266 used in zone 0.
The enclosure contains aluminum and is considered to
present a potential risk of ignition by impact or friction.
Care must be taken into account during installation and use
to prevent impact or friction. pening the housing cover.