Specifications; Electrical Data - Danfoss VLT AutomationDrive FC 302 Operating Manual

90–315 kw, enclosure size d1h–d8h
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Specifications

10 Specifications

10.1 Electrical Data

10.1.1 Electrical Data for Enclosures D1h–D4h, 3x200–240 V
®
VLT
AutomationDrive FC 302
High/normal overload
(High overload=150% current during 60 s.
Normal overload=110% current during 60 s)
Typical shaft output at 230 V [kW]
Typical shaft output at 230 V [hp]
Enclosure size
Output current (3-phase)
Continuous (at 230 V) [A]
Intermittent (60 s overload) (at 230 V) [A]
Continuous kVA (at 230 V) [kVA]
Maximum input current
Continuous (at 230V) [A]
Maximum number and size of cables per phase
Mains, motor, brake, and load share [mm
Maximum external mains fuses [A]
Estimated power loss at 230 V [W]
3)
Efficiency
10
10
Output frequency [Hz]
Heat sink overtemperature trip [°C (°F)]
Control card overtemperature trip [°C (°F)]
Table 10.1 Electrical Data for Enclosures D1h/D3h, Mains Supply 3x200–240 V AC
1) For fuse ratings, see chapter 10.7 Fuses and Circuit Breakers.
2) Typical power loss is at normal conditions and expected to be within
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies for
dimensioning of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control
card power consumptions are included. For power loss data according to EN 50598-2, refer to www.danfoss.com/vltenergyefficiency. Options and
customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each add only 4 W.
3) Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy
efficiency class, see chapter 10.4 Ambient Conditions. For part load losses, see www.danfoss.com/vltenergyefficiency.
96
VLT® AutomationDrive FC 302
2
(AWG)]
1)
2), 3)
Danfoss A/S © 09/2018 All rights reserved.
N45K
HO
NO
45
55
60
75
160
190
240
209
64
76
154
183
2x95 (2x3/0)
315
1482
1505
0.97
0–590
110 (230)
75 (167)
± 15% (tolerance relates to variety in voltage and cable conditions). These
N55K
HO
NO
55
75
75
100
D1h/D3h
190
240
285
264
76
96
183
231
2x95 (2x3/0)
350
1794
2398
0.97
0–590
110 (230)
75 (167)
MG34U502