Troubleshooting
Check for a defective power card.
WARNING 48, 1.8 V supply low
The 1.8 V DC supply used on the control card is outside of
the allowable limits. The supply is measured on the control
card.
Troubleshooting
Check for a defective control card.
If an option card is present, check for
overvoltage.
WARNING 49, Speed limit
The warning is shown when the speed is outside of the
specified range in parameter 4-11 Motor Speed Low Limit
[RPM] and parameter 4-13 Motor Speed High Limit [RPM].
When the speed is below the specified limit in
parameter 1-86 Trip Speed Low [RPM] (except when starting
or stopping), the drive trips.
9
9
ALARM 50, AMA calibration failed
Contact the Danfoss supplier or Danfoss service
department.
ALARM 51, AMA check U
The settings for motor voltage, motor current, and motor
power are wrong.
Troubleshooting
Check the settings in parameters 1-20 to 1-25.
ALARM 52, AMA low I
The motor current is too low.
Troubleshooting
Check the settings in parameter 1-24 Motor
Current.
ALARM 53, AMA motor too big
The motor is too large for the AMA to operate.
ALARM 54, AMA motor too small
The motor is too small for the AMA to operate.
ALARM 55, AMA parameter out of range
The AMA cannot run because the parameter values of the
motor are outside of the acceptable range.
ALARM 56, AMA interrupted by user
The AMA is manually interrupted.
ALARM 57, AMA internal fault
Try to restart the AMA. Repeated restarts can overheat the
motor.
ALARM 58, AMA Internal fault
Contact the Danfoss supplier.
90
VLT® AutomationDrive FC 302
and I
nom
nom
nom
Danfoss A/S © 09/2018 All rights reserved.
WARNING 59, Current limit
The current is higher than the value in
parameter 4-18 Current Limit. Ensure that the motor data in
parameters 1-20 to 1-25 is set correctly. Increase the current
limit if necessary. Ensure that the system can operate safely
at a higher limit.
WARNING 60, External interlock
A digital input signal indicates a fault condition external to
the drive. An external interlock has commanded the drive
to trip. Clear the external fault condition. To resume
normal operation, apply 24 V DC to the terminal
programmed for external interlock, and reset the drive.
WARNING/ALARM 61, Feedback error
An error is detected between calculated speed and speed
measurement from feedback device.
Troubleshooting
Check the settings for warning/alarm/disabling in
parameter 4-30 Motor Feedback Loss Function.
Set the tolerable error in parameter 4-31 Motor
Feedback Speed Error.
Set the tolerable feedback loss time in
parameter 4-32 Motor Feedback Loss Timeout.
WARNING 62, Output frequency at maximum limit
If the output frequency reaches the value set in
parameter 4-19 Max Output Frequency, the drive issues a
warning. The warning ceases when the output drops
below the maximum limit. If the drive is unable to limit
the frequency, it trips and issues an alarm. The latter may
happen in the flux mode if the drive loses control of the
motor.
Troubleshooting
Check the application for possible causes.
Increase the output frequency limit. Ensure that
the system can operate safely at a higher output
frequency.
ALARM 63, Mechanical brake low
The actual motor current has not exceeded the release
brake current within the start delay time window.
WARNING 64, Voltage limit
The combination of load and speed requires a motor
voltage higher than the actual DC-link voltage.
WARNING/ALARM 65, Control card over temperature
The cutout temperature of the control card is 85 °C
(185 °F).
Troubleshooting
Check that the ambient operating temperature is
within the limits.
Check for clogged filters.
Check the fan operation.
Check the control card.