Electrical Installation
Terminal
27
Parameter 5-12
Digital Input
29
Parameter 5-13
Digital Input
20
5
5
37
Table 5.2 Digital Input/Output Terminal Descriptions
Terminal
39
42
Parameter 6-50
50
53
Analog Input 1
54
Analog Input 2
55
Table 5.3 Analog Input/Output Terminal Descriptions
5.9.3 Wiring to Control Terminals
The control terminals are located near the LCP. The control
terminal connectors can be unplugged from the drive for
convenience when wiring, as shown in Illustration 5.35.
64
Digital input/output terminals
Parameter
Default
setting
[2] Coast
For digital input or
Terminal 27
inverse
output. Default
setting is input.
[14] JOG
Terminal 29
Common for digital
inputs and 0 V
potential for 24 V
supply.
STO
When not using the
optional STO feature,
a jumper wire is
required between
terminal 12 (or 13)
and terminal 37. This
set-up allows the
drive to operate with
factory default
programming values.
Analog input/output terminals
Parameter
Default
setting
Common for analog
output.
[0] No
Programmable analog
Terminal 42
operation
output. 0–20 mA or
Output
4–20 mA at a
maximum of 500 Ω.
+10 V DC
10 V DC analog
supply voltage for
potentiometer or
thermistor. 15 mA
maximum.
Parameter
Reference
Analog input. For
group 6-1*
voltage or current.
Switches A53 and
A54 select mA or V.
Parameter
Feedback
group 6-2*
Common for analog
input.
Danfoss A/S © 09/2018 All rights reserved.
VLT® AutomationDrive FC 302
Either solid or flexible wire can be connected to the
control terminals. Use the following procedures to connect
Description
or disconnect the control wires.
NOTICE
Minimize interference by keeping control wires as short
as possible and separate from high-power cables.
Connecting wire to control terminals
1.
2.
3.
Description
Illustration 5.37 Connecting Solid Control Wires
Illustration 5.38 Connecting Flexible Control Wires
Strip 10 mm (0.4 in) of the outer plastic layer
from the end of the wire.
Insert the control wire into the terminal.
For a solid wire, push the bare wire into
the contact. See Illustration 5.37.
For a flexible wire, open the contact by
inserting a small screwdriver into the
slot between the terminal holes and
push the screwdriver inward. See
Illustration 5.38. Then, insert the stripped
wire into the contact, and remove the
screwdriver.
Pull gently on the wire to ensure that the contact
is firmly established. Loose control wiring can be
the source of equipment faults or reduced
performance.
12 13 18 19 27 29 32 33
12 13 18 19 27 29 32 33
MG34U502