11.2 International/North American Default Parameter Settings

Setting parameter 0-03 Regional Settings to [0] International or [1] North America changes the default settings for some
parameters. Table 11.2 lists those parameters that are affected.
Parameter
Parameter 0-03 Regional Settings
Parameter 0-71 Date Format
Parameter 0-72 Time Format
Parameter 1-20 Motor Power [kW]
Parameter 1-21 Motor Power [HP]
Parameter 1-22 Motor Voltage
Parameter 1-23 Motor Frequency
Parameter 3-03 Maximum Reference
Parameter 3-04 Reference Function
Parameter 4-13 Motor Speed High Limit
3)
[RPM]
Parameter 4-14 Motor Speed High Limit [Hz]
Parameter 4-19 Max Output Frequency
Parameter 4-53 Warning Speed High
Parameter 5-12 Terminal 27 Digital Input
Parameter 5-40 Function Relay
Parameter 6-15 Terminal 53 High Ref./Feedb.
Value
Parameter 6-50 Terminal 42 Output
Parameter 14-20 Reset Mode
Parameter 22-85 Speed at Design Point
[RPM]
3)
Parameter 22-86 Speed at Design Point [Hz]
Parameter 24-04 Fire Mode Max Reference
Table 11.2 International/North American Default Parameter Settings
1) Parameter 1-20 Motor Power [kW] is only visible when parameter 0-03 Regional Settings is set to [0] International.
2) Parameter 1-21 Motor Power [HP] is only visible when parameter 0-03 Regional Settings is set to [1] North America.
3) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [0] RPM.
4) This parameter is only visible when parameter 0-02 Motor Speed Unit is set to [1] Hz.

11.3 Parameter Menu Structure

MG34U502
Operating Guide
International default parameter value
International
DD-MM-YYYY
24 h
1)
2)
230 V/400 V/575 V
50 Hz
50 Hz
Sum
1500 RPM
50 Hz
4)
100 Hz
1500 RPM
Coast inverse
Alarm
50
Speed 0-HighLim
Manual reset
1500 RPM
50 Hz
50 Hz
Danfoss A/S © 09/2018 All rights reserved.
North American default parameter value
North America
MM/DD/YYYY
12 h
1)
2)
208 V/460 V/575 V
60 Hz
60 Hz
External/Preset
1800 RPM
60 Hz
120 Hz
1800 RPM
External interlock
No alarm
60
Speed 4-20 mA
Infinite auto reset
1800 RPM
60 Hz
60 Hz
11
11
145