Electrical Installation
5.7 Connecting Regen/Load Share Terminals
The optional regeneration/load share terminals are found at the top of the drive. For drives with IP21/IP54 enclosures, the
wiring is routed through a cover surrounding the terminals. Refer to Illustration 5.5.
•
Size the wiring according to the current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data.
•
Comply with local and national electrical codes for cable sizes.
Procedure
1.
Remove 2 plugs (for either top entry or side entry) from the terminal cover.
2.
Insert cable fittings into the terminal cover holes.
3.
Strip a section of the outer cable insulation.
4.
Position the stripped cable through the fittings.
5.
Connect the DC(+) cable to the DC(+) terminal, and secure with 1 M10 fastener.
6.
Connect the DC(-) cable to the DC(-) terminal, and secure with 1 M10 fastener.
7.
Tighten the terminals in accordance with chapter 10.8.1 Fastener Torque Ratings.
MG34U502
Operating Guide