Electrical Installation

5.7 Connecting Regen/Load Share Terminals

The optional regeneration/load share terminals are found at the top of the drive. For drives with IP21/IP54 enclosures, the
wiring is routed through a cover surrounding the terminals. Refer to Illustration 5.5.
Size the wiring according to the current of the drive. For maximum wire sizes, see chapter 10.1 Electrical Data.
Comply with local and national electrical codes for cable sizes.
Procedure
1.
Remove 2 plugs (for either top entry or side entry) from the terminal cover.
2.
Insert cable fittings into the terminal cover holes.
3.
Strip a section of the outer cable insulation.
4.
Position the stripped cable through the fittings.
5.
Connect the DC(+) cable to the DC(+) terminal, and secure with 1 M10 fastener.
6.
Connect the DC(-) cable to the DC(-) terminal, and secure with 1 M10 fastener.
7.
Tighten the terminals in accordance with chapter 10.8.1 Fastener Torque Ratings.