Danfoss VLT AutomationDrive FC 302 Operating Manual page 76

90–315 kw, enclosure size d1h–d8h
Hide thumbs Also See for VLT AutomationDrive FC 302:
Table of Contents

Advertisement

Wiring Configuration Exampl...
Speed
Start/Stop (18)
Illustration 8.2 Start/Stop with Safe Torque Off
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
D IN
29
8
8
D IN
32
D IN
33
D IN
37
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 8.6 Wiring Configuration for Pulse Start/Stop
Speed
Latched Start (18)
Stop Inverse (27)
Illustration 8.3 Latched Start/Stop Inverse
74
VLT® AutomationDrive FC 302
Parameters
Function
Setting
Parameter 5-10
[9] Latched
Terminal 18
Start
Digital Input
Parameter 5-12
[6] Stop Inverse
Terminal 27
Digital Input
*=Default value
Notes/comments:
If parameter 5-12 Terminal 27
Digital Input is set to [0] No
operation, a jumper wire to
terminal 27 is not needed.
Danfoss A/S © 09/2018 All rights reserved.
FC
+24 V
12
+24 V
13
D IN
18
D IN
19
COM
20
D IN
27
29
D IN
D IN
32
D IN
33
+10 V
50
A IN
53
A IN
54
COM
55
A OUT
42
COM
39
Table 8.7 Wiring Configuration for Start/Stop with Reversing
and 4 Preset Speeds
Parameters
Function
Setting
Parameter 5-10
[8] Start
Terminal 18
Digital Input
Parameter 5-11
[10] Reversing*
Terminal 19
Digital Input
Parameter 5-12
[0] No
Terminal 27
operation
Digital Input
Parameter 5-14
[16] Preset ref
Terminal 32
bit 0
Digital Input
Parameter 5-15
[17] Preset ref
Terminal 33
bit 1
Digital Input
Parameter 3-10
Preset Reference
Preset ref. 0
25%
Preset ref. 1
50%
Preset ref. 2
75%
Preset ref. 3
100%
*=Default value
Notes/comments: