Control Settings; To Input The Operation Setting And The Frequency Setting From The Terminal Control - Hyundai N700E Instruction Manual

Hide thumbs Also See for N700E:
Table of Contents

Advertisement

N700E INSTRUCTION MANUAL
`
3.2

Control Settings

This is an example of a common connection. Please refer to Digital Operator, for the detailed use of the
digital operator.
3.2.1
To input the operation setting and the frequency setting from the terminal
control
Power Supply 3 Phase
200V : 200 ~ 240V
400V : 380 ~ 480V
(50/60Hz ±10%)
Intelligent Input
(Digital Input)
FM Output
Monitor
(0~10Vdc)
Frequency
Setting Input
(1kΩ, 1W)
Current Input
4~20mA
(Procedure)
(1) Please make sure that the connections are secured correctly.
(2) Turn the MCCB on to supply power to the inverter.
(The LED "POWER" on the operator should illuminate)
(3) Set the terminal with the frequency setting selection.
Set A01 as the indication code, press the (FUNC) key once. (Code values are shown)
Set 1(Terminal) with (UP/DOWN) key, press the (STR) key once to set the operation setting for the
operator.(Indication code turns back to A01.)
(4) Set terminal with the operation setting selection.
Set A02 as indication code, press the (FUNC) key once.
Set 1(terminal) with the (UP/DOWN) key, press the (STR) key once to set the operation setting for the
operator.(Indication code turns back to A02.)
(5) Set Monitor mode
When monitoring the output frequency, set indication code to d001, and press the (FUNC) key.
Or when monitoring the operation direction, set indication code to d04, and press the (FUNC) key.
(6) Input starting operation setting.
Turn ON between [FW] and [CM1] of terminal.
Apply voltage [O] - [L] or current [OL]-[L] of terminal to start operation.
(7) Input ending operation setting.
Turn OFF between [FW] and [CM1] to slowly stop.
R
S
T
P24
1
2
3
4
5
6
CM1
R+
RS-485
(option)
R-
FM
CM1
H
DC 0~10V
O
DC 4~20mA
OI
L
Fig 3-1 Setting diagram from the terminal control
3-4
N700E
U
V
W
P
RB
AL1
AL2
AL0
SC
S2
S1
DOP
R+
R-
CM1
12
11
CM2
G
Earth Ground
T1
T2
IM
T3
Alarm Relay
Output
Safety Signal
(option)
RS485
(RJ-45)
Intelligent
Output

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents