13.6. Compressor Reverse Rotation Protection Control

• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and indoor
heat exchanger is 2.5 C or less for continuous 2 minutes, compressor will stop and restart automatically.
• Time Delay Safety Control is activated before the compressor restart.
• This is to prevent compressor from rotate reversely when there is an instantaneous power failure.

13.7. Dew Prevention control

• To prevent dew formation at indoor unit discharge area.
• This control start if:-
- Cooling mode or Quit mode is activated.
- Remote Control setting temperature is less than 25 C.
- Fan speed is at Lo or QLo.
- Room temperature is constant (±1 C) for 30 minutes.
- Compressor is continuously running.
• Fan speed, angle of horizontal louver (vertical airflow angle) and angle of vertical louver (horizontal airflow angle) will be adjusted
accordingly in this control.
- Fan speed will be increased slowly if the unit is in quiet mode and Lo fan speed.
- The angle of horizontal louver will be changed as table below:
Airflow direction auto control
- The angle of vertical louver will be changed as table below:
Airflow direction auto control
• Dew prevention stop condition.
- Remote Control setting temperature is less than 25 C.
- Fan speed is at Lo or QLo.
- Select Power operation.
Airflow direction manual control
Airflow direction manual control