Removing The Heat Exchanger For Degree Of Protection Ip55 - Siemens SINAMICS S120 Manual

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

4.5.4.2

Removing the heat exchanger for degree of protection IP55

The heat exchanger must be removed so that the DC busbars can be connected when the
cabinet units are lined up next to one another.
Removing the heat exchanger
Loosen the 6 screws
deflector plate.
Release the lateral screws
towards the front.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
at the front side of the upper air
, and remove the air baffle
Open the fast release connection of the front coolant con-
nection
.
Remove the connecting cable for the fan power supply at
connector X160
.
Close the vent valve, remove the vent hose
Remove the heat exchanger from the cabinet towards the
front.
Open the fast release connector of the rear coolant connec-
tion.
Electrical installation
4.5 Connections
.
81