Siemens SINAMICS S120 Manual page 312

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Diagnostics
8.2 LEDs on the CU320-2 DP Control Unit
LED
Color
Red
OPT
(OPTION)
Green
Red
RDY and
Red
COM
RDY and
Orange
OPT
Any individual response of the LED OPT is described for the respective Option Board.
1)
310
State
Description, cause
Flashing
PROFIBUS master is sending wrong parameteri-
light
zation/configuration data
0.5 Hz
Flashing
Cyclic bus communication has been interrupted
light
or could not be established
2 Hz
Off
The electronics power supply is missing or out-
side the permissible tolerance range.
Component is not ready.
Option board not installed or no associated drive
object has been created.
Steady
Option board is ready.
light
Flashing
Depends on the option board used
light
0.5 Hz
Continuous
Depends on the option board used
light
Flashing
Depends on the option board used
light
0.5 Hz
Flashing
At least one fault is present in this component.
light
Option board not ready (e.g. after switching on).
2 Hz
Flashing
Bus fault - communication has been interrupted
light
2 Hz
Flashing
The firmware of the connected option board is
light
being updated.
0.5 Hz
Remedy
Adapt configuration between
master/controller and CU
Correct the fault
Check power supply and/or
component
.
1)
.
1)
.
1)
Remedy and acknowledge
fault
Correct the fault
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A

Advertisement

Table of Contents
loading

Table of Contents