9.24 dv/dt filter compact plus Voltage Peak Limiter
Note
Setting pulse frequencies
It is permissible to set pulse frequencies in the range between the rated pulse frequency and
the relevant maximum pulse frequency when a dv/dt filter compact plus Voltage Peak Limiter
is used. "Current derating as a function of the pulse frequency" of the converter must be
observed here (refer to the Technical data).
Table 9- 48
Max. pulse frequency when a dv/dt filter compact plus VPL is used for units with a rated pulse frequency of 2
kHz
Article No.
6SL3725-
1TE32-1AA3
1TE32-6AA3
1TE33-3AA3
1TE35-0AA3
1TE41-4AS3
Table 9- 49
Max. pulse frequency when a dv/dt filter compact plus VPL is used for units with a rated pulse frequency of
1.25 kHz
Article No.
6SL3725-
1TE36-1AA3
1TE37-5AA3
1TE38-4AA3
1TE41-0AA3
1TE41-2AA3
1TE41-4AA3
424
Unit rating [kW]
Output current for a
pulse frequency of 2 kHz [A]
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 VDC)
110
132
160
250
800
Unit rating [kW]
Output current for a
pulse frequency of 1.25 kHz [A]
Line voltage 380 ... 480 V 3 AC
(DC link voltage 510 ... 720 VDC)
315
400
450
560
710
800
Max. pulse frequency when a dv/dt filter
210
260
310
490
1330
Max. pulse frequency when a dv/dt filter
605
745
840
985
1260
1405
Equipment Manual, 04/2020, A5E37067587A
is used
4 kHz
4 kHz
4 kHz
4 kHz
4 kHz
is used
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
2.5 kHz
Cabinet Modules liquid cooled