9.53 W36, Heat Exchanger Module prepared for installation on the right in the cabinet lineup

9.53
W36, Heat Exchanger Module prepared for installation on the right
in the cabinet lineup
Availability of option
This option is available for the following S120 Cabinet Modules:
● Heat Exchanger Modules
Description
With the option, a fixed pipe connection is routed downward on the left-hand side.
As a consequence, the Heat Exchanger Module can be installed at the right-hand end of the
drive lineup and connected to the deionized water circuit on the converter side. The
connecting parts (pipe couplings) are provided with the converter.
9.54

W43, release valve in the deionized water circuit

Availability of option
This option is available for the following S120 Cabinet Modules:
● Heat Exchanger Modules
Description
A release valve is installed between the intake and return in the converter-side deionized
water circuit.
The valve limits the pressure of the circulating pumps. It ensures a minimum flow rate by
opening as soon as the pressure exceeds the value set at the valve.
Note
The pressure is only regulated by the release valve
Adjust the "ball valve to reduce the pressure at the intake of the converter-side deionized
water circuit" (77.3) to "open" in order for the release valve to be able to regulate the
pressure.