Siemens SINAMICS S120 Manual page 183

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Parallel connection of Motor Modules to increase power rating
The following rules must be observed when connecting Motor Modules in parallel:
● Up to four identical Motor Modules can be connected in parallel.
● A common Control Unit is required whenever the modules are connected in parallel.
● The motor supply cables must be the same length (symmetrical design).
● Power must be supplied to the Motor Modules from a common DC busbar.
● A derating factor of 5% must be taken into consideration, regardless of the number of
modules connected in parallel.
● For motors with multi-winding systems, carefully observe the notes in the Low Voltage
Configuration Manual
● For motors with a single-winding system, the length of the supply cables must be kept to
a minimum. The cables lengths are listed in the following tables.
Figure 6-15
Figure 6-16
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Motor with electrically isolated winding systems supplied by a parallel connection of
S120 Motor Modules
Motor with common winding system supplied by a parallel connection of S120 Motor
Modules
Cabinet Modules
6.3 Motor Modules
181

Advertisement

Table of Contents
loading

Table of Contents