Siemens SINAMICS S120 Manual page 41

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Figure 2-6
The intake temperatures in the plant/system side raw water circuit must always be at least
7K below the intake temperatures in the deionized water circuit. This ensures that the
cooling power of the Heat Exchanger Module of the deionized water circuit, specified in the
technical data, can be dissipated to the raw water circuit.
For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A
Maximum output current as a function of coolant temperature of the deionized water
circuit on the converter side
System overview
2.11 Derating data
39

Advertisement

Table of Contents
loading

Table of Contents