Siemens SINAMICS S120 Manual page 38

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

System overview
2.10 System data
General data
Plant-side raw water circuit
Minimum system pressure
with respect to the atmos-
phere
Max. system pressure with
respect to atmosphere
Pressure drop at the heat
exchanger at rated flow
rate
Recommended pressure
range
Intake temperature of
liquid coolant
Deionized water circuit in the
converter
Max. system pressure with
respect to atmosphere
Pressure drop at the heat
sink at rated volumetric
flow
Recommended pressure
range
Intake temperature of
liquid coolant
Shock protection
Cabinet system
Paint finish
Power data for the basic version, power rating can be increased using a parallel connection.
1)
Electromagnetic compatibility (EMC)
Emitted interference
Noise immunity
36
180 kPa
600 kPa
50 kPa ... 90 kPa
250 kPa
Dependent on ambient temperature and cabinet degree of protection, condensation is
not permitted
<IP55: +5 ... +38 °C (recommended temperature range: +25 ... +30 °C)
IP55: +5 ... +33 °C (recommended temperature range: +25 ... +30 °C)
(anti-freeze essential for temperature range between 0° C and 5° C; recommended
anti-freeze agent: "Antifrogen N" supplied by Clariant)
600 kPa
150 kPa (incl. hose connections)
160 ... 250 kPa
Dependent on ambient temperature and cabinet degree of protection, condensation is
not permitted
<IP55: 0 ... 45 °C without derating, > 45 ... 50 °C see derating characteristics
IP55: 0 ... 40 °C without derating, > 40 ... 45 °C see derating characteristics
(anti-freeze essential for temperature range between 0° C and 5° C; recommended
anti-freeze agent: "Antifrogen N" and "Antifrogen L" from the Clariant company)
EN 50274 and DGUV regulation 3 when used for the intended purpose
Rittal TS 8, doors with double-barb lock, floor panels in the form of a tray to collect any
leakage water. Cable entry from below through a neoprene mat
RAL 7035 (indoor requirements)
Category C3 (second environment) according to EN 61800-3
Use in the first and second environment according to EN 61800-3
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A