Diagnostics

8.11 LEDs on the SMC30 Sensor Module

8.11
LEDs on the SMC30 Sensor Module
Table 8- 19
Meaning of the LEDs on the SMC30 Sensor Module
LED
Color
RDY
---
(READY)
Green
Orange
Red
Green/red
Green /
orange
or
red / or-
ange
OUT > 5V
-
Orange
320
State
Description
Off
The electronics power supply is missing or outside the permissible tolerance range.
Steady
The component is ready for operation and cyclic DRIVE-CLiQ communication is
light
taking place.
Steady
DRIVE-CLiQ communication is being established.
light
Steady
This component has at least one fault.
light
Remark:
The LED is activated irrespective of whether the corresponding messages have
been reconfigured.
Flashing
Firmware is being downloaded.
0.5 Hz
2 Hz flash-
Firmware download is complete. Waiting for POWER ON.
ing light
2 Hz flash-
Detection of the components via LED is activated (p0144).
ing light
Remark:
Both options depend on the LED status when module recognition is activated via
p0144 = 1.
Off
The electronics power supply is missing or outside the permissible tolerance range.
Power supply ≤ 5 V.
Steady
The electronics power supply for the measuring system is available.
light
Measuring system supply > 5 V
Notice:
You must ensure that the connected encoder can be operated with a 24 V power
supply.
If an encoder that is designed for a 5 V supply is operated with a 24 V supply, this
can destroy the encoder electronics.