Siemens SINAMICS S120 Manual page 384

Cabinet modules liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Options
9.14 K50, Sensor Module Cabinet-Mounted SMC30
X521/X531 encoder connection 2 for HTL/TTL/SSI encoder with open-circuit monitoring
Table 9- 29
Connector
Max. connectable cross-section: 1.5 mm²
Note
Operation of unipolar HTL encoders
When unipolar HTL encoders are used, terminal block A*, B*, and R* must be jumpered with
M encoder (-X531).
Table 9- 30
Connector
Max. connectable cross-section: 1.5 mm²
Measuring current via temperature sensor connection: 2 mA
Accuracy of the temperature measurement:
1)
- KTY: ±7 °C (including evaluation)
- PT1000: ±5 °C (PT1000 tolerance class B according to EN 60751 including evaluation)
- PTC: ±5 °C (including evaluation)
382
Encoder connection X521
Terminal
Signal name
1
A
2
A*
3
B
4
B*
5
R
6
R*
7
CTRL
8
M
Encoder connection X531
Terminal
Signal name
1
P encoder 5 V / 24 V
2
M encoder
3
-Temp
1)
4
+Temp
1)
5
Clock
6
Clock*
7
Data
8
Data*
Technical data
Incremental signal A
Inverted incremental signal A
Incremental signal B
Inverted incremental signal B
Reference signal R
Inverted reference signal R
Control signal
Ground
Technical data
Encoder power supply
Ground for encoder power supply
Temperature sensor KTY84-1C130 /
PT1000 / PTC
Bimetallic switch with NC contact
SSI clock
Inverted SSI clock
SSI data
Inverted SSI data
Cabinet Modules liquid cooled
Equipment Manual, 04/2020, A5E37067587A