3.5.4

Voltage Sensing Module

The Voltage Sensing Module VSM10 measures the actual line voltage values for the Active
Line Module.
3.5.5

SMC30 Sensor Module

The SMC30 (Sensor Module Cabinet-Mounted 30) evaluates motor encoder signals. The
sensor module transfers the speed and actual position value to the Control Unit via the internal
DRIVE-CLiQ communication interface.
Note
If an encoder fails, the mode can be switched over to "encoderless".
3.5.6

Precharging

To prevent overcurrents and temporary overvoltages in the DC link when the line voltage is
connected, the DC-link capacitors must be precharged. The DC link is precharged via the
auxiliary supply.
The precharging circuit comprises the following components:
● Precharging transformer
● Diode bridge
● Precharging resistors
● Contactor for switching on and off
● Circuit-breaker
Detailed information about interconnecting the precharging components is provided in the
circuit manual. The component mounting locations are provided in the layout diagram.
Designation
Precharging time
Precharging current in three-phase 400 V supply
with 3.3 kV; and 4.16 kV single connection
Discharging time of the DC link T
The time can vary depending on the system
1)
SINAMICS SM150 6SL3810-7NN38-0AA1
Operating Instructions Rev.201910281406 EXAMPLE
1)
1)
DISCH
3.5 Description of the components
Value
20 s
20 A
≈ 300 s
Description
35