iCOM Control Board DIP Switch Settings for Analog Input Setup

Plug Connector
P7-1 (+) / P7-2 (-)
P11-1 (+) / P11-2 (-)
P11-3 (+) / P11-4 (-)
P11-5 (+) / P11-6 (-)
P11-7 (+) / P11-8 (-)
P12-1 (+) / P12-2 (-)
P12-3 (+) / P12-4 (-)
P12-5 (+) / P12-6 (-)
P12-7 (+) / P12-8 (-)
P13-1 (+) / P13-2 (-)
P13-3 (+) / P13-4 (-)
P13-5 (+) / P13-6 (-)
* Default Setting
Input/Output Type
NTC Thermistor
PTC Thermistor
Analog Voltage: 0 to +5V
Analog Voltage: 0 to +10V
Analog Current: 4 to 20mA
+5V Output
Analog Voltage: 0 to +5V
Analog Voltage: 0 to +10V
Analog Current: 4 to 20mA
+5V Output
Analog Voltage: 0 to +5V
Analog Voltage: 0 to +10V
Analog Current: 4 to 20mA
+5V Output
Analog Voltage: 0 to +5V
Analog Voltage: 0 to +10V
Analog Current: 4 to 20mA
+5V Output
NTC Thermistor
PTC Thermistor
NTC Thermistor
NTC Scroll Thermistor
NTC Thermistor
NTC Scroll Thermistor
134
Setting
* Software (ASW1 = 1)
Software (ASW1 = 0)
* Sw2-1: On / Sw2-2: Off
Sw2-1: Off / Sw2-2: Off
Sw2-1: On / Sw2-2: On
None
* Sw2-3: On / Sw2-4: Off
Sw2-3: Off / Sw2-4: Off
Sw2-3: On / Sw2-4: On
None
* Sw2-5: On / Sw2-6: Off
Sw2-5: Off / Sw2-6: Off
Sw2-5: On / Sw2-6: On
None
* Sw2-7: On / Sw2-8: Off
Sw2-7: Off / Sw2-8: Off
Sw2-7: On / Sw2-8: On
None
* Software (ASW2 = 1)
Software (ASW2 = 0)
Sw2-9: On
* Sw2-9: Off
Sw2-10: On
* Sw2-10: Off