Emerson Liebert iCOM Training And Service Manual page 115

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

iCOM
Controls Training and Service Manual
Factory Settings Parameters, page 3 of 9
Menu
SMALL DISPLAY
Line
(Large Display)
A112
(Password)
A113
DS CYCLE (Digital Scroll Cycle)
A114
DS HT (High Temp Digital Scroll)
A115
DS SWB (Digital Scroll Switchback)
A116
LP TYPE (Low Pressure Device Type)
LP PH1 (Low Pressure Threshold
A117
Phase 1)
LP PH2 (Low Pressure Threshold
A118
Phase 2)
A119
LC PRE *** (Liquid Control Pre-time)
A120
LC POST *** (Liquid Control Post-time)
*** Note: Parameters A119 and A120 for the electrically actuated ball type water
regulating valves are displayed but, they are not active at this time.
Note 1: Low Pressure Threshold Phase 1 (Menu Line A117):
The displayed pressure value for menu line A117 – Low Pressure Threshold
Phase 1 is determined by the programmed selection on menu line A132 – Heat
Rejection Control Type. The pressure displayed is as follows:
Fanspeed Condenser
Lee-Temp Condenser
If menu line A132 - Heat Rejection Control Type is changed, the value on menu
line A117 is updated automatically.
ADVANCED MENU Continued
Parameter
Menu Line A133
Water/Glycol
114
Default
Range
-
15 sec
No, 10 – 30 sec
268°F
33 – 392°F
250°F
33 – 392°F
Analog
Analog, Switch
See
0.0 – 145 psia
Note 1
See
0.0 – 145 psia
Note 2
-
sec
-
sec
Menu Line A117
50 psia
75 psia
75 psia
Control
Board
Safe
-
-
CSF
CSF
CSF
CSF
CSF
CSF
CSF
CSF