User Menu Parameters - Password: 1490; Setpoint Parameters - Emerson Liebert iCOM Training And Service Manual

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

The following pages show all of the various parameters, default values and
programming ranges.

USER MENU Parameters - Password: 1490

Small Display parameters are shown in CAPITAL LETTERS
Large Display parameters are shown in (Parenthesis)
Parameters may be System or Unit and either Read only or Read/Write.
Note: Parameters may be a System or Unit View when Networked
Note: The column indicated by TW1 (Teamwork Mode 1) is a list of
parameters that are shared when TW1 is selected for the control operation.

Setpoint Parameters

Parameter
Menu
SMALL DISPLAY
Line
(Large Display)
U101
(Password)
TEMP SET
U102
(Temperature Setpoint)
HUM SET
U103
(Humidity Setpoint)
HUM CTRL
U104
(Humidity Control Type)
U105
SUP LIM (Supply Limit)
SUP TEMP
U106
(Supply Limit Temp Value)
BACK TSP (Backup
U107
Temperature Setpoint)
iCOM
Control Training and Service Manual
Menu Parameters
Default
-
73°F
50%
PRED
(Predictive)
Dsabl
(Disable)
41°F
73°F
75
Shared
Range
in TW1
-
-
41 - 104°F
Yes
1 - 80%
Yes
REL, COMP,
PRED
(Relative,
Yes
Compensated,
Predictive)
Enabl, Dsabl
(Enable,
Yes
Disable)
41 - 77°F
Yes
41 - 104°F
Yes
Control
Board
Safe
-
CSF
CSF
CSF
CSF
CSF
CSF