Diagnostics/Service Mode, page 7 of 7 – Read Only
Menu
Line
S367
HUM PROB (Status Humidifier Problem)
S368
DT1 (not on Large Display)
S369
DT2 * (Status DT2 Glycol/Room)
S370
DT3 * (Status DT3 Room/Setpoint)
S371
MIN CW (Status Min CW)
S372
COND 1 (not on Large Display)
S373
COND 2 (not on Large Display)
Note:
*
S369: Active: Compressorized and Freecooling available.
Off: Compressorized cooling only available.
S370: Active: If Low Pressure condition occurs freecooling will be disabled
for 1 hour and system will operate on compressors only.
Off: Restarts compressor after 10 minutes.
S371: Active: Above the Minimum Chilled Water temperature setpoint.
S372 OFF: Below the Minimum Chilled Water Temperature Setpoint
iCOM
SERVICE MENU's Continued
Parameter
SMALL DISPLAY
(Large Display)
95
Control Training and Service Manual
Range
OK, ACT (OK, Active)
-
OFF, ACT (OK, Active)
OFF, ACT (OK, Active)
OFF, ACT (OK, Active)
-
-