Controls Training and Service Manual
P53: Motorized Ball Valve #1 (MBV-1)
P53-1:
24 VAC Out to MVB-1
P53-2:
24 VAC Out
P53-3:
MVB-1 Signal to MP
P54: Motorized Ball Valve #2 (MBV-2)
P54-1:
24 VAC Out to MVB-2
P54-2:
24 VAC Out
P54-3:
MVB-2 Signal to MP
P61: Optional Intellislot 12 VDC Power Supply, connect only if optional device is
used.

P63: NOT Used

P64: Ethernet Port

Connects the Large Display to the Control Board using a crossover cable or
connects the Control Board to the switch using a straight patch cable when
networking.
P65: Site Monitoring Signals when the Intellislot is not used
P65-1:
+5 VDC to TS 78
P65-2:
-5 VDC to TS 77
Must be re-connected to the optional Intellislot for communications when used.
P66: Unit Display Power CAN Bus Connection (Digital Signal).
P67: Temperature/Humidity Assembly Power CAN Bus Connection (Digital
Signal).
TB1: 24 VAC
TB1-1:
24 VAC (T2)
TB1-2:
24 VAC (T3)
TB1-3:
24 VAC (T4)
TB1-4:
24 VAC (T5)

E1/ E2/ E3/ E4: Transformer Grounds

Test Points for DC Voltage on Control Board
TP1:
DC Gnd
TP2:
DC Gnd
TP3:
DC Gnd – A out
TP4:
+ 3.3 VDC
TP5:
+ 12 VDC
P53-4:
24 VAC Gnd (E4)
P53-5:
No connection
P54-4:
24 VAC Gnd (E4)
P54-5:
no connection
TB1-5:
E1 (G2)
TB1-6:
E2 (G3)
TB1-7:
E3 (G4)
TB1-8:
E4 (G5)
TP6:
+ 5 VDC
TP7:
+ 12 VDC – A out
TP8:
TP9:
+ 5 VDC – A out
TP10