Example D: Four Units with Small Displays in 2 Groups with Large Wall Mounted
Displays
The following references parameters in the Network Menu.
Remote Wall Mounted Large Displays
S802
Number of Connected Units
S813
Large Display IP Address
S814
Large Display Netmask IP
Address
S815
Large Display Gateway IP
Address
S818
Large Display U2U Address
S819
Large Display U2U Group
Large Control Boards
S836
Control Board IP Address
S837
Control Board Netmask IP
Address
S838
Control Board Gateway IP
Address
S841
Control Board U2U Address
S842
U2U Group
iCOM
Control Training and Service Manual
1 - 32
192.168.254.xxx
255.255.255.000 (must be the same
in each unit)
000.000.000.000 (must be the same
in each unit)
33, 34
1, 2
192.168.254.xxx
255.255.255.000 (must be the same
in each unit)
000.000.000.000 (must be the same
in each unit)
1 or 2
1, 2
55