Temperature/Humidity Board Dip Switch #1 Settings; Temperature/Humidity Board Jumper Settings; Default Setting - Emerson Liebert iCOM Training And Service Manual

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

Temperature/Humidity Board DIP Switch #1 Settings

SW1 - 1
SW1 - 2
Off
Off
On
Off
Off
On
On
On

Temperature/Humidity Board Jumper Settings

Jumper
P2
P3
P4
E10 – E13

* Default Setting

Jumper P3 CAN Bus Termination: The correct position of this jumper is
dependant on your environment. If the board is physically the first or last node on
the CAN Bus, the jumper needs to be shunted across pins 2 – 3 (Default position).
Otherwise position the shunt across pins 1 – 2.
Jumper P4
Jumper P3
iCOM
SW1 - 3
SW1 - 4
Off
Off
Off
Off
Off
Off
Off
Off
Type
BDM Header
CAN Termination
Programming
Serial Port
137
Control Training and Service Manual
SW1 - 5
SW1 - 6
On
Off
On
Off
On
Off
On
Off
Setting
* Open
* Shunt on Pins 2 & 3
* Open
* Open
Jumper P2
DIP Switch #1
Comments
Internal T/H Sensor
Sensor A
Sensor B
Sensor C