Emerson Liebert iCOM Training And Service Manual page 127

Large systems microprocessor
Hide thumbs Also See for Liebert iCOM:
Table of Contents

Advertisement

iCOM
Controls Training and Service Manual
Motorized Ball Valve Settings - Large Display only, page 1 of 1
Menu
Line
A401
(Password)
A403
(Max Setpoint/Output)
A404
(U4 Actual/Setpoint/Ouput Change)
A405
(U3A Actual/Setpoint/Ouput Change)
A406
(U3B Actual/Setpoint/Ouput Change)
A407
(U2A Actual/Setpoint/Ouput Change)
A408
(U2B Actual/Setpoint/Ouput Change)
A409
(U1 Actual/Setpoint/Ouput Change/Delay)
A410
(L1 Actual/Setpoint/Ouput Change/Delay)
A411
(L2A Actual/Setpoint/Ouput Change)
A412
(L2B Actual/Setpoint/Ouput Change)
A413
(L3 Actual/Setpoint/Ouput Change)
A414
(Min Setpoint/Output)
A415
(Start Delay Output/Time)
A416
(Stop Delay Setpoint/Output/Time)
A417
(Dig. Scroll Filter)
A418
(Offset)
A419
(MBV 1 Pressure/Position)
A420
(MBV 2 Pressure/Position)
A421
(MVB Reinit)
A422
(Reading Interval)
Note: Parameters A403 – A422 are for the electrically actuated ball type water
regulating valves, they are not active at this time.
ADVANCED MENU's Continued
Parameter
(Large Display)
126
Range
-
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100% /
0 – 1800 sec
0 – 580 psia / 0 – 100% /
0 – 1800 sec
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 580 psia / 0 – 100%
0 – 100% / 0 – 600 sec
0 – 580 psia / 0 – 100% /
0 – 1800 sec
1 - 100
± 26 psia
± 999 psia / 0 – 100%
± 999 psia / 0 – 100%
0 = No, 1 = Yes
0 – 600 sec