Outputs Screens; Auxiliary Inputs Screens; Pulse Kw Setup; Analog Kw Setup - Emerson MultiFlex CUB-II Installation And Operation Manual

Condensing unit board
Table of Contents

Advertisement

8.2.8. Outputs Screens

Out #1 Comp
Out #2 Defrost
Out #3 CondFan1
Out #4 Remote
Out #5 Remote
Out #6 Remote
Out #7 Remote
Out #8 Alarm
The two screens under the heading "Output"
are where you assign each of the eight relay out-
puts to a controlled device in the condensing unit
system.
Sensor Control
Input Type
Comp
The compressor
CondFan1
Condenser fan #1
CondFan2
Condenser fan #2
CondFan3
Condenser fan #3
CondFan4
Condenser fan #4
Defrost
The defrost output
Refr Sol
Refrigeration solenoid
Evap Fan
Case evaporator fan
Alarm
The alarm output (turns ON when
alarm condition exists on CUB)
SensCtrl1
Output controlled by sensor control
loop #1
SensCtrl2
Output controlled by sensor control
loop #2
Remote
Unused by CUB, but may be con-
trolled by E2 or Einstein remotely
NDF
Not defined
Table 8-4 - CUB Sensor Control Output Types

8.2.9. Auxiliary Inputs Screens

8.2.9.1.

Pulse KW Setup

Pulse KW Setup
KWH per
Pulse: 20
KW Per Pulse
If you are using a pulse accumulation type
KW transducer, you must enter the number of
KW per pulse for this transducer in this field.
58 • MultiFlex CUB-II and CUB-TD I&O Guide
Description
8.2.9.2.

Analog KW Setup

Analog KW Setup
Volts
Min:
0
Max:
5
KW Analog
If you are using an analog KW transducer,
you must enter the voltage range of the input and
the range of KW values the voltage corresponds
to. This information is different for each KW
Transducer and depends on the line voltage and
current transducer (CT) rating. Refer to your
KW transducer's installation instructions.
Under the Volts column, enter the minimum
and maximum sensor output voltages. Under the
KW column, enter the minimum and maximum
KW represented by the min/max voltage range.
8.2.9.3.

Linear 1 and 2 Setup

Linear 1
Volts Output
Min:
0
Max:
5
Linear 2
Volts Output
Min:
0
Max:
5
Linear 1 and 2
If you wish to use one or both of the Linear 1
and Linear 2 sensor types used by the sensor
control applications, you must specify the volt-
age range of the sensor output and the range of
values those voltages represent.
Under the Volts column, enter the minimum
and maximum sensor output voltages. Under the
Output column, enter the minimum and maxi-
mum engineering unit values represented by the
min/max voltage range.
KW
0
5000
Setup
0
100
Setup
0
1000
026-1705 Rev 7 06-APR-2010